CHP units
- 2013 год
CHP units
General:
Gas-fueled power units in soundproof shield, frequency 50 Hz, voltage 400 V, 3-phase alternating current.
MAN gas-fueled power units on natural gas
Station model | Power |
Efficiency (general)
|
Engine model | Gas consumption at 100 % load | |
Electrical (COP – Continuous Power) | Thermal (maximal) | ||||
kW | kW | % |
m3/h |
||
GGK35M | 35 | 55 | 80,45 | MAN E0834 E312 | 11,1 |
GGK50M | 50 | 79 | 88,17 | MAN E0834 E302 | 15,3 |
GGK70M | 70 | 109 | 88,17 | MAN E0836 E302 | 20,8 |
GGK100M | 100 | 145 | 87,22 | MAN E0836 LE302 | 27,7 |
GGK130M | 130 | 193 | 91,54 | MAN E2676 E302 | 36,1 |
GGK150M | 140 | 207 | 89,28 | MAN E2876 E312 | 40,3 |
GGK200M | 200 | 283 | 85,95 | MAN E2876 LE302 | 54,2 |
GGK200M | 200 | 267 | 88,03 | MAN E2676 LE202 | 54,2 |
GGK200M | 200 | 284 | 87,78 | MAN E2876 LE212 | 56,9 |
GGK250M | 250 | 374 | 91,50 | MAN E3262 E302 | 75,1 |
GGK300M | 300 | 382 | 87,12 | MAN E3268 LE242 | 77,8 |
GGK350M | 350 | 443 | 87,42 | MAN E3268 LE212 | 94,4 |
GGK400M | 400 | 548 | 86,54 | MAN E3262 LE232 | 115,3 |
GGK500M | 500 | 645 | 85,90 | MAN E3262 LE202 | 141,7 |
MAN gas power units on special gas (drilling gas, biogas, sewage gas, pyrolysis gas and landfill gas)
Model | Power | Efficiency | Engine | Gas consumption at 100 % load | |
Electrical (to be specified depending on gas composition) | Thermal | ||||
kW | kW | % | m3/h | ||
GGK60M | 60 | to be specified depending on gas composition | MAN E0834 LE302 | to be specified depending on gas composition | |
GGK70M | 70 | MAN E0834 LE322 | |||
GGK100M | 100 | MAN E0836 LE302 | |||
GGK130M | 120 | MAN E2876 TE302 | |||
GGK200M | 180 | MAN E2876 LE302 | |||
GGK200M | 200 | MAN E2876 LE202 | |||
GGK200M | 200 | MAN E2676 LE212 | |||
GGK300M | 300 | MAN E3268 LE252 | |||
GGK300M | 300 | MAN E3268 LE262 | |||
GGK350M | 350 | MAN E3268 LE222 | |||
GGK350M | 350 | MAN E3268 LE232 | |||
GGK400M | 400 | MAN E3262 LE242 | |||
GGK500M | 500 | MAN E3262 LE212 |
Power unit scope of supply
1. MAN gas engine (Germany)
2. Single-bearing generator Leroy Somer (France)
3. Welded steel frame with antivibration mounts
4. Lubrication system with water-oil radiator and filter
5. Fuel system with fuel filters, microprocess throttle control unit and gas metering device
6. Heat recovery system installed on one frame with gas power unit
7. Inlet system with air filter
8. Exhaust system with silencer and expansion joint
Control system
Control system is based on microprocess controller that provides parallel operation of cogeneration plant in auto mode. It consists of operator’s display with software and cable 25 m. The system carries out parallel operation of units with automatic load distribution by ensuring the following:
1. Independent automatic mode
2. Parameter control function of cogeneration plant
3. Emergency alarm
4. Operation visualization
5. Operator’s software
6. Close monitoring
7. Function of parallel operation with circuit
8. Parallel operation mode of typical plants
Specified life limit till overhaul is 50 000 (60 000 for non-turbine) operating hours if technical maintenance and operation instructions are observed. After 50 000 (60 000 for non-turbine) operating hours it is necessary to carry out major overhaul of the engine and replace such items as crank bearings, pistons, rings, sleeves or replace entire diesel engine.